{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5EF36-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5EF36-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5EF36-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF36-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA1132-5EF36-0AB0, 3-pole, 32 A, TM240 release, 187 kA at 240 V.","salesMarkdown":"Its interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — that SCCR headroom means it clears high-fault bolted faults without upstream cascade in most distribution panels. Dimensions are 130 mm tall, 76.2 mm wide, and 70 mm deep, so it fits standard 3-pole MCCB panel cutouts and busbar spacing. Above that, derating kicks in: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. The adjustable response time tr max is 1 s, which gives some room for downstream short-time delay coordination with smaller MCCBs or MCBs. For DC network applications, the manufacturer directs to the 3VA device manual for switching power values.","metaTitle":"Siemens 3VA1132-5EF36-0AB0 MCCB, 32 A, 187 kA at 240 V","metaDescription":"Siemens SENTRON 3VA1132-5EF36-0AB0 molded case circuit breaker, 3-pole, 32 A rated current, 187 kA breaking capacity at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"22 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=522055&mlfb=3VA1132-5EF36-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF36-0AB0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1132-5EF36-0AB0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source to 3VA1132-5EF36-0AB0?","answer":"The 3VA1110-5EE32-0DC0 is a lower-breaking-capacity sibling in the same SENTRON 3VA family, but it uses a different release and frame size — verify cutout dimensions and SCCR requirements before substituting."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a SENTRON 3VA series MCCB, it carries the standard Siemens declarations for RoHS and REACH compliance, plus IEC/EN 60947-2 certification for molded case circuit breakers. Specific UL listing status should be confirmed per the exact order code variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5EF36-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5EF36-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}