{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5EF36-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5EF36-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5EF36-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF36-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA1132-5EF36-0AE0, 3-pole, 32 A rated current, TM240 thermal-magnetic release, 187 kA breaking capacity at 240 VAC, 70 mm depth, 76.2 mm width, 130 mm height.","salesMarkdown":"The Siemens SENTRON 3VA1132-5EF36-0AE0 is a 3-pole molded case circuit breaker rated for 32 A continuous current, holding that rating all the way up to 50 °C ambient — no derating needed until you cross 55 °C, where it steps to 31 A, and 30 A at 65 °C. Breaking capacity is the headline: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. For compliance documentation: the SENTRON 3VA series typically ships with CE, UL, and CSA certifications, and the manufacturer provides RoHS and REACH declarations. Specific certificate numbers should be confirmed at quote time against your jurisdiction — UL 489 for North America, IEC 60947-2 for global installations. ## Integration notes for the panel builder The 130 mm height and 70 mm depth fit standard distribution board cutouts; the 76.2 mm width (3 inches) is the 3-pole footprint. No communication function or voltage trigger on this variant — it's a straight line-protection device, not a smart breaker.","metaTitle":"Siemens SENTRON 3VA1132-5EF36-0AE0 MCCB, 32 A, 3-Pole, 187 k","metaDescription":"Siemens SENTRON 3VA1132-5EF36-0AE0 molded case circuit breaker, 32 A rated, 3-pole, TM240 release, 187 kA breaking capacity at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11325EF360AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=859&mlfb=3VA1132-5EF36-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF36-0AE0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The 187 kA figure at 240 V makes it suitable for high-fault service entrance applications."},{"question":"Where can I buy 3VA1132-5EF36-0AE0 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for volume or single-piece requirements."},{"question":"Will 3VA1132-5EF36-0AE0 drop into a panel specified for 3VA1110-5EE36-0AA0 without rewiring?","answer":"Both are 3-pole SENTRON 3VA breakers with the same 70 mm depth and 76.2 mm width, so the physical footprint matches. The difference is the current rating and release type — 3VA1110-5EE36-0AA0 is a lower-amp variant. Verify the continuous current and breaking capacity requirements against your load before swapping."},{"question":"What compliance documentation does this brand provide for 3VA1132-5EF36-0AE0?","answer":"The SENTRON series typically carries CE, UL, and CSA certifications, with RoHS and REACH declarations available from Siemens. UL 489 and IEC 60947-2 are the applicable standards. Request specific certificate copies at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5EF36-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5EF36-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}