{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5EF36-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5EF36-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5EF36-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF36-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 series, IEC frame 160, 3-pole molded case circuit breaker, breaking capacity class M (Icu=55kA @ 415V), TM240 thermal-magnetic trip unit, In=32A, overload Ir=22A...32A, short-circuit Ii=5...10 x In, clamp connection, includes 1 auxiliary switch HP and 1 trip alarm switch HP.","salesMarkdown":"The TM240 thermal-magnetic trip unit gives you an adjustable overload (Ir) from 22 A to 32 A and a fixed magnetic short-circuit pickup (Ii) at 5 to 10 times In — so for a 32 A breaker, that's 160 to 320 A instantaneous. That range suits motor branch circuits or feeder protection where you need to ride through inrush without nuisance tripping. Clamp connection terminals accept copper or aluminum conductors up to the frame's rated cross-section. The factory-fitted auxiliary switch (HP) and trip alarm switch (HP) give you remote status feedback — the auxiliary tracks the breaker's on/off position, the alarm signals a trip event. Both are wired to a terminal block on the breaker face, so you don't need to open the cover to check state.","metaTitle":"Siemens 3VA1132-5EF36-0AG0 Circuit Breaker, 55kA @ 415V, 32A","metaDescription":"Siemens 3VA1132-5EF36-0AG0 IEC 3-pole circuit breaker, 55kA breaking capacity at 415V, 32A TM240 trip unit. Current lifecycle stage. Available to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=434920&mlfb=3VA1132-5EF36-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF36-0AG0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-5EF36-0AG0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"The 3VA1132-5EF36-0AG0 has a rated ultimate breaking capacity (Icu) of 55 kA at 415 V AC, placing it in breaking capacity class M. This means it can safely interrupt fault currents up to 55 kA at that voltage without damage."},{"question":"What trip unit does this breaker use?","answer":"It uses a TM240 thermal-magnetic trip unit. The overload protection (Ir) is adjustable from 22 A to 32 A, and the short-circuit protection (Ii) is fixed at 5 to 10 times the rated current In (32 A), so 160 to 320 A instantaneous pickup."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5EF36-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5EF36-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}