{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5GE42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5GE42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5GE42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5GE42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 MCCB, 4-pole, breaking capacity class M, Icu=55kA @ 415V, TM220 thermal-magnetic trip unit, In=32A, overload protection Ir=22A...32A, short-circuit protection Ii=10 x In.","salesMarkdown":"## 4-pole IEC frame 160 MCCB with TM220 trip The In=32A continuous rating and adjustable overload protection Ir=22A...32A let you fine-tune the thermal pickup to match the protected conductor or load. Short-circuit protection is fixed at Ii=10 x In (320A magnetic pickup), which is typical for line protection on distribution feeders rather than motor starting. The 100% N-conductor protection means the neutral pole is fully rated and will trip with the phase poles — important for 4-wire systems where neutral overcurrent must be cleared. The lifecycle stage for this order code is listed as current, so it remains in the active Siemens catalog and is not subject to a last-time-buy or phase-out notice at this time. The ZD00 suffix indicates a customer-specific version — in this case a nut keeper kit for DC Power OEM in China. That means the base breaker (3VA1132-5GE42-0AA0) is a standard Siemens catalog item, but the full code with suffix is a configured variant. Verify the OEM-specific hardware is what your BOM calls for before ordering.","metaTitle":"Siemens 3VA1132-5GE42-0AA0-ZD00 4-pole IEC breaker, 55kA @ 4","metaDescription":"Siemens 3VA1132-5GE42-0AA0-ZD00 IEC frame 160 MCCB, 4-pole, 55kA breaking capacity @ 415V, TM220 thermal-magnetic trip unit, In=32A. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667712&mlfb=3VA1132-5GE42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5GE42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-5GE42-0AA0-ZD00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability."},{"question":"What is the breaking capacity of this breaker?","answer":"Icu=55kA at 415V, which is the class M breaking capacity for the 3VA1 IEC frame 160 platform."},{"question":"What does the ZD00 suffix mean on this order code?","answer":"The ZD00 suffix identifies a customer-specific variant that includes a nut keeper kit for DC Power OEM in China. The base breaker is the standard 3VA1132-5GE42-0AA0."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5GE42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5GE42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}