{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6ED36-0AA0, molded case circuit breaker, 3-pole, TM210 release, 32 A, 220 kA at 240 V AC, IP40 front.","salesMarkdown":"That's a standard fixed-trip curve for general distribution; you don't get the flexibility of an electronic trip, but you also don't need a separate power supply for the trip unit. The interrupting ratings are the headline: 220 kA at 240 V AC, 154 kA at 415 V AC, 121 kA at 440 V AC, and 17 kA at 500 V and 690 V AC. At 690 V the 17 kA rating is still respectable for a 32 A frame, but if your system runs at 480 V or 600 V class, the 121 kA at 440 V gives you a good reference point for coordination studies. The 32 A rating holds flat from 40 °C to 50 °C, then derates to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C. That's a shallow derating curve — only 2 A lost over a 30 °C rise — which means the breaker runs cool and you don't have to oversize the frame for a warm enclosure. The power loss is 10.6 W maximum, so heat dissipation inside the panel is manageable even with several breakers ganged together. Physical dimensions: 76.2 mm wide (3 in), 130 mm tall (5.12 in), 70 mm deep (2.76 in).","metaTitle":"Siemens 3VA1132-6ED36-0AA0 SENTRON MCCB, 3-Pole, 32 A, TM210","metaDescription":"Siemens 3VA1132-6ED36-0AA0 SENTRON molded case circuit breaker, 3-pole, 32 A, TM210 release, 220 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1,5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=2180&mlfb=3VA1132-6ED36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6ED36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-6ED36-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting rating of this MCCB at 240 V?","answer":"220 kA at 240 V AC — that's a high-fault-current rating suitable for large transformer secondaries or high-capacity busway feeds."},{"question":"What does the TM210 release mean?","answer":"TM210 means a fixed thermal-magnetic trip: 32 A continuous (no adjustable thermal dial) and a magnetic short-circuit pickup at 10× In (320 A). It's a standard fixed-trip curve for distribution circuits."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}