{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6ED36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6ED36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6ED36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6ED36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6ED36-0AH0, molded case circuit breaker, 3-pole, 200 A rated continuous Iu, TM120M thermal-magnetic release, 220 kA at 240 V, 110 kW at 400 V AC-3, IP40 front, 158 mm height.","salesMarkdown":"## Siemens SENTRON 3VA1132-6ED36-0AH0 — 200 A MCCB, Starter Protection Version It carries a 220 kA breaking capacity at 240 V, 154 kA at 415 V, 76 kA at 440 V, 30 kA at 500 V, and 3 kA at 690 V — per the datasheet, these are the short-circuit current ratings the device can safely interrupt at each voltage level. The TM120M release provides thermal protection for overloads and magnetic (instantaneous) protection for short circuits, with the thermal curve calibrated for motor starting inrush. Above that, derating applies: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. ## Motor Switching Duty (AC-3) Rated for AC-3 motor switching duty: 55 kW at 230 V and 110 kW at 400 V. This is the power it can switch under the IEC AC-3 utilization category — starting and stopping squirrel-cage motors during running, not just isolating. The 110 kW at 400 V figure is the one most site electrical engineers will verify against their motor nameplate.","metaTitle":"Siemens 3VA1132-6ED36-0AH0 SENTRON MCCB, 200 A, 220 kA at 24","metaDescription":"Siemens SENTRON 3VA1132-6ED36-0AH0 molded case circuit breaker, 200 A rated continuous, 220 kA breaking at 240 V. Starter protection version, TM120M release. Current production. Qu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Height":"158 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"76 kA","at 500 V":"30 kA","at 690 V":"3 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"194 A","at 60 °C":"188 A","at 65 °C":"182 A","at 70 °C":"176 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Starter protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"200 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM120M","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 230 V":"55 000 W","Operating power / at AC-3 / at 400 V":"110 000 W","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / li max.":"2 800 A","Adjustable response value current / li min.":"1 200 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"I","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027589&mlfb=3VA1132-6ED36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6ED36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-6ED36-0AH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 3VA1132-6ED36-0AH0's listed height?","answer":"The listed height is 158 mm."},{"question":"What is 3VA1132-6ED36-0AH0's breaking capacity at 240 V?","answer":"The breaking capacity at 240 V is 220 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6ED36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6ED36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}