{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1, molded case circuit breaker, 3-pole, 32 A (40 °C), 220 kA at 240 V, TM240 overcurrent release, line protection.","salesMarkdown":"## SCCR and selectivity At 415 V the interrupting capacity is 154 kA, dropping to 121 kA at 440 V, and 17 kA at 500 V and 690 V. That spread means the breaker stays coordinated downstream of a transformer with a 480 V secondary — the high 240 V rating is what you'd use for the main on a 208Y/120 panel. Rated 32 A from 40 °C through 50 °C, then 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C. That's a shallow derating curve — you lose only 2 A over the full 30 °C rise — so it holds its rating well in a warm enclosure. The case is 70 mm deep, 76.2 mm wide, 130 mm tall, which fits the standard 3-pole MCCB footprint on DIN rail or a panel-mount base. Front protection is IP40, meaning no gasket needed for a dry indoor panel.","metaTitle":"Siemens 3VA1132-6EF32-0AA0 SENTRON MCCB, 32A, 220kA at 240V","metaDescription":"Siemens 3VA1132-6EF32-0AA0 SENTRON 3-pole MCCB, 32A rated at 40°C, 220kA interrupting at 240V. TM240 release, line protection. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=402583&mlfb=3VA1132-6EF32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1132-6EF32-0AA0 at 240 V?","answer":"220 kA at 240 V, which covers high-fault utility feeds and transformer secondaries."},{"question":"What overcurrent release does 3VA1132-6EF32-0AA0 use?","answer":"TM240 thermal-magnetic release — handles overload and short-circuit protection without an external trip unit."},{"question":"Where can I buy 3VA1132-6EF32-0AA0 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}