{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 series, IEC frame 160, breaking capacity class H, Icu=70kA @ 415V, 3-pole, line protection TM240 ATAM, In=32A, overload Ir=22A…32A, short-circuit Ii=5…10 x In, nut keeper kit, 2 auxiliary switches HP.","salesMarkdown":"## What the 70 kA @ 415 V means for your panel ## Trip settings and protection range The TM240 unit is adjustable: overload protection (Ir) spans 22 A to 32 A, and short-circuit protection (Ii) is set at 5 to 10 times In — so between 160 A and 320 A for the magnetic pickup. That wide Ii range lets the commissioning engineer tune for motor inrush or transformer energization without nuisance tripping, while the thermal element handles the continuous load curve. The nut keeper kit and two auxiliary switches (HP) are factory-fitted, saving a panel-builder step. The 160 A frame occupies roughly the same footprint as the 250 A frame in the same series, so if you are retrofitting into an existing enclosure, verify the gland-plate clearance for the outgoing terminals. The auxiliary switches are pre-wired to a common terminal block; no additional wiring of microswitches is needed.","metaTitle":"Siemens 3VA1132-6EF32-0AB0 IEC Frame 160 MCCB, 70kA @ 415V","metaDescription":"Siemens 3VA1132-6EF32-0AB0 circuit breaker, IEC frame 160, class H Icu=70kA @ 415V, 3-pole, TM240 ATAM, In=32A. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=29632&mlfb=3VA1132-6EF32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA1132-6EF32-0AB0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"What is the breaking capacity of this breaker?","answer":"Icu = 70 kA at 415 V AC, which is class H for the IEC frame 160. That is the maximum short-circuit current it can safely interrupt under test conditions."},{"question":"What are the overload and short-circuit trip ranges?","answer":"Overload protection Ir is adjustable from 22 A to 32 A. Short-circuit protection Ii is adjustable from 5 to 10 times In, so 160 A to 320 A magnetic pickup."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}