{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6EF32-0AG0, 3-pole molded case circuit breaker, 32 A rated continuous current, 220 kA breaking capacity at 240 V, TM240 thermal-magnetic release, line protection version.","salesMarkdown":"The 220 kA breaking capacity at 240 V tells you this thing can interrupt a serious fault without the arc re-striking; at 415 V it still holds 154 kA, and at 690 V it's 17 kA. What you see is what you get: a TM240 release that holds 32 A through 50 °C ambient (–), then starts derating linearly to 28.8 A at 70 °C. That flat 32 A band through 50 °C is useful if the panel sits in a warm machine room; you don't lose headroom until the ambient climbs past 50 °C. The 3VA1132-6EF32-0AG0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep. It mounts via screw-clamp to a backplate or DIN rail adapter. It ships with one auxiliary switch and one trip alarm switch, high-performance (HP) contacts. No undervoltage release, no shunt trip — if you need remote tripping, you're adding an external release module.","metaTitle":"Siemens 3VA1132-6EF32-0AG0 MCCB, 32 A, 220 kA at 240 V","metaDescription":"Siemens SENTRON 3VA1132-6EF32-0AG0 molded case circuit breaker, 3-pole, 32 A rated, 220 kA breaking at 240 V. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"22 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=103924&mlfb=3VA1132-6EF32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF32-0AG0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}