{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA1132-6EF32-0KC0, molded case circuit breaker, 3-pole, 32 A rated continuous current, TM240 overcurrent release, 220 kA breaking capacity at 240 V, shunt trip, 2 auxiliary switches HQ, IP40 front.","salesMarkdown":"Its breaking capacity hits 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — so it handles high-fault utility feeds and transformer secondaries without cascading upstream. That keeps the BOM simple but means you size the breaker to the load, not the other way around. The shunt trip (STL) and two HQ auxiliary switches come integrated, saving a panel-builder the labor of snapping on add-on modules later. The 3VA1132-6EF32-0KC0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep. The 76.2 mm width (three 25.4 mm pole pitches) matches the standard SENTRON 3VA mounting footprint, so swapping into an existing 3VA panel cutout is a straight drop-in. At 55 °C it derates to 30.72 A, at 60 °C to 30.08 A, at 65 °C to 29.44 A, and at 70 °C to 28.8 A. That's a gentle slope — about 3.2 A lost over the full 30 °C rise — so a 30 A continuous load at 60 °C still has headroom. The TM240 release's thermal element tracks this curve, so no manual adjustment needed.","metaTitle":"SENTRON 3VA1132-6EF32-0KC0 MCCB, 32 A, 220 kA at 240 V","metaDescription":"SENTRON 3VA1132-6EF32-0KC0 molded case circuit breaker, 32 A rated continuous current, 220 kA breaking capacity at 240 V. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1132-6EF32-0KC0","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class H Icu=70kA @ 415V 3-pole, line protection TM240, ATAM, In=32A overload protection Ir=22A...32A short-circuit protection Ii=5...10 x In nut keeper kit shunt trip (STL) 220-250V DC, 208-277V AC 2 auxiliary switches HQ","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"22 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=146452&mlfb=3VA1132-6EF32-0KC0"},"ai":{"faq":[{"question":"Will 3VA1132-6EF32-0KC0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"The 76.2 mm width and 70 mm depth match the same 3VA frame footprint, so it fits the same panel cutout and bus bar spacing. But the 3VA1132-6EF32-0KC0 carries a 32 A TM240 release with shunt trip and two HQ auxiliaries — verify the control wiring for the shunt trip and auxiliary contacts match your existing circuit before committing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}