{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6EF36-0AH0, molded case circuit breaker, 3-pole, 32 A (40 °C), breaking capacity 220 kA at 240 V, line protection, TM240 release.","salesMarkdown":"At 40 °C it holds 32 A continuous, and its interrupting capacity reaches 220 kA at 240 V — enough to clear high-fault industrial feeders without cascading upstream breakers. The 220 kA rating at 240 V drops to 154 kA at 415 V and 121 kA at 440 V, then to 17 kA at 500 V and 690 V — the steep roll-off above 500 V means this MCCB is sized for 240/415 V distribution panels, not 690 V drives. Thermal derating is minimal up to 50 °C (still 32 A), then drops 1 A per 5 °C step to 30 A at 70 °C. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm high — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling.","metaTitle":"Siemens 3VA1132-6EF36-0AH0 SENTRON MCCB, 32 A, 220 kA at 240","metaDescription":"Siemens SENTRON 3VA1132-6EF36-0AH0 molded case circuit breaker, 3-pole, 32 A rated at 40 °C, 220 kA breaking capacity at 240 V. Line protection, TM240 release. Active production. Q","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11326EF360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=511144&mlfb=3VA1132-6EF36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1132-6EF36-0AH0 at 240 V?","answer":"220 kA at 240 V, dropping to 154 kA at 415 V and 121 kA at 440 V, then to 17 kA at 500 V and 690 V."},{"question":"Where can I buy 3VA1132-6EF36-0AH0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What is the rated current of 3VA1132-6EF36-0AH0 at 40 °C?","answer":"32 A at 40 °C, with minimal derating to 30 A at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}