{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0AM0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0AM0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0AM0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0AM0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1132-6EF36-0AM0, IEC frame 160 MCCB, 3-pole, breaking capacity class H (70kA @ 415V), 32A, TM240 thermal-magnetic trip, adjustable Ir 22-32A, Ii 5-10xIn, clamp terminals, with 2 aux switches + 1 alarm switch.","salesMarkdown":"The 3VA1132-6EF36-0AM0 is a 3-pole IEC frame 160 molded-case circuit breaker rated at 32 A continuous, with a breaking capacity of 70 kA at 415 V (class H). The thermal-magnetic trip unit (TM240) gives you adjustable overload protection from 22 A to 32 A via the Ir dial, and short-circuit pickup (Ii) adjustable from 5 to 10 times the rated current (160–320 A). That adjustability means you can tune it to the actual load cable and motor starting inrush, not just the nameplate. This breaker lands in a standard IEC distribution or motor control center panel. It uses clamp (box-lug) terminals for incoming and outgoing conductors — no special tooling beyond a screwdriver and a torque wrench.","metaTitle":"Siemens 3VA1132-6EF36-0AM0 MCCB, 32A, 70kA @ 415V","metaDescription":"Siemens 3VA1132-6EF36-0AM0 IEC frame 160 MCCB, 3-pole, 32A, 70kA breaking capacity at 415V. Active lifecycle, available to order. RFQ for current pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027509&mlfb=3VA1132-6EF36-0AM0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0AM0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB?","answer":"It has a breaking capacity of 70 kA at 415 V (class H), which means it can safely interrupt faults up to that level."},{"question":"How do I get pricing and availability for 3VA1132-6EF36-0AM0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0AM0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0AM0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}