{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6EF36-0CH0, molded case circuit breaker, 3-pole, 32 A rated continuous current Iu, line protection, TM240 overcurrent release, 220 kA at 240 V.","salesMarkdown":"## Siemens SENTRON 3VA1132-6EF36-0CH0 — 32 A MCCB for Line Protection Breaking capacity is the headline spec here: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and still 17 kA at 690 V. The 690 V rating at 17 kA also makes it usable in 600 V class Canadian and some IEC industrial networks. The 76.2 mm width (3-pole) and 130 mm height fit the SENTRON 3VA family footprint, so it drops into existing SENTRON panel layouts without re-drilling. Above that, it derates linearly: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. The undervoltage release (UVR) is built in; it will trip the breaker if control voltage drops below about 70% of rated. This is standard for applications where a loss of control power must open the main disconnect — emergency stops, safety circuits, or sequential start interlocks. The integrated auxiliary trip module is order code 3VA9608-0BB24, a separate line item if you need a spare.","metaTitle":"Siemens 3VA1132-6EF36-0CH0 SENTRON MCCB, 32 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA1132-6EF36-0CH0 molded case circuit breaker, 32 A rated, 3-pole, line protection. Breaking capacity 220 kA at 240 V. Current lifecycle. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"22 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=337265&mlfb=3VA1132-6EF36-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-6EF36-0CH0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm availability and current pricing — no stock figures or price lists are published here."},{"question":"What is the breaking capacity of 3VA1132-6EF36-0CH0 at 415 V?","answer":"154 kA at 415 V, which is the standard IEC test voltage for three-phase distribution in much of the world. This rating ensures the breaker can clear high-fault currents at that voltage without damage."},{"question":"Does 3VA1132-6EF36-0CH0 include an undervoltage release?","answer":"Yes, it is factory-equipped with an undervoltage release (UVR) that trips the breaker when control voltage drops below the dropout threshold. The auxiliary contact configuration is 2 auxiliary switches plus 1 trip alarm switch (HQ)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}