{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class H, 3-pole circuit breaker, 32A, 70kA @ 415V, TM240 line protection, undervoltage release 208-230V AC.","salesMarkdown":"The Siemens 3VA1132-6EF36-0DA0 is a 3-pole IEC frame 160 circuit breaker with breaking capacity class H, rated for 70 kA at 415 V AC. It carries a TM240 thermal-magnetic trip unit set at In=32 A, with adjustable overload protection Ir from 22 A to 32 A and short-circuit protection Ii adjustable from 5 to 10 times In. The TM240 thermal-magnetic trip provides line protection for cable and busbar; the adjustable Ir (22-32 A) lets you dial in the exact load current without changing the breaker body. The Ii range of 5-10x In (160-320 A) covers motor-start inrush and selective coordination needs. ## Panel integration Clamp-type terminals accept copper conductors without lugging — strip, insert, torque. The UVR coil draws its control voltage from a separate 208-230 V AC supply; verify the control transformer rating if sharing with other loads.","metaTitle":"Siemens 3VA1132-6EF36-0DA0 Circuit Breaker, 32A, 70kA @ 415V","metaDescription":"Siemens 3VA1132-6EF36-0DA0 IEC frame 160 circuit breaker, 70kA breaking capacity at 415V, 32A TM240 overload protection, undervoltage release. Current lifecycle stage. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=380697&mlfb=3VA1132-6EF36-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0DA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of 3VA1132-6EF36-0DA0?","answer":"IEC frame 160, breaking capacity class H at 70 kA / 415 V, 3-pole, TM240 thermal-magnetic trip unit set at 32 A with adjustable overload Ir 22-32 A and short-circuit Ii 5-10x In, plus a factory-fitted undervoltage release 208-230 V AC."},{"question":"Where can I buy 3VA1132-6EF36-0DA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}