{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6EF36-0DC0, molded case circuit breaker, 3-pole, 32 A rated at 40 °C, 220 kA breaking at 240 V, line protection, undervoltage release, 2 auxiliary switches HQ.","salesMarkdown":"That 220 kA figure drops to 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 / 690 V, so the voltage class of your system dictates the actual SCCR you get. The 70 mm depth, 76.2 mm width, and 130 mm height fit the standard SENTRON 3VA footprint — it bolts into the same bus-bar and mounting pattern as other 3VA frame sizes, making a swap or upgrade straightforward without re-drilling the panel. Rated current holds at 32 A from 40 °C through 50 °C, then drops to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C. That's a gentle derating curve — only 2 A lost over a 30 °C rise — so you can pack it into a warm enclosure without a big capacity penalty. The maximum power loss is 13.1 W, which is modest for a 32 A MCCB; still, if you're stacking multiple breakers in a sealed panel, sum the losses and check the internal temperature rise against the derating table.","metaTitle":"SENTRON 3VA1132-6EF36-0DC0 MCCB, 32 A, 3-Pole, 220 kA at 240","metaDescription":"Siemens SENTRON 3VA1132-6EF36-0DC0 molded case circuit breaker, 32 A, 3-pole, 220 kA breaking capacity at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11326EF360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=293919&mlfb=3VA1132-6EF36-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0DC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-6EF36-0DC0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. The voltage class of your system determines the SCCR you get from this breaker."},{"question":"Does 3VA1132-6EF36-0DC0 include an undervoltage release?","answer":"Yes, it ships with an undervoltage release (UVR) as standard, plus two auxiliary switches (HQ design) for status feedback."},{"question":"What are the mounting dimensions of this breaker?","answer":"Depth 70 mm, width 76.2 mm, height 130 mm. It fits the standard SENTRON 3VA footprint and bolts into the same bus-bar pattern as other 3VA frame sizes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}