{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6EF36-0JC0, molded case circuit breaker, 3-pole, 32 A rated continuous current Iu, TM240 thermal-magnetic overcurrent release, 220 kA breaking capacity at 240 V, IP40 front protection.","salesMarkdown":"## Line protection MCCB with thermal-magnetic release Its TM240 thermal-magnetic overcurrent release handles both overload and short-circuit trip curves without external power. Breaking capacity is specified at multiple voltage levels: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V — the 240 V and 415 V figures cover the common low-voltage distribution fault-current ranges in North American and IEC panels respectively. Above that, derating is linear: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. ## Auxiliary and shunt trip configuration Dimensions are 76.2 mm wide (3-pole base), 130 mm tall, and 70 mm deep. Front protection is IP40. The breaker mounts via screw terminals and fits standard Siemens SENTRON 3VA panel footprints. No trip indicator is fitted on this variant.","metaTitle":"Siemens 3VA1132-6EF36-0JC0 SENTRON MCCB, 32 A, 220 kA at 240","metaDescription":"Siemens SENTRON 3VA1132-6EF36-0JC0 molded case circuit breaker, 32 A rated, 3-pole, TM240 release, 220 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"22 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=123288&mlfb=3VA1132-6EF36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA1132-6EF36-0JC0 and how is it quoted for volume purchases?","answer":"This part is sourced through independent industrial-automation distribution and quoted to order against an RFQ. Availability and pricing are confirmed at quote time; no stock count or price is published here."},{"question":"What is the breaking capacity of 3VA1132-6EF36-0JC0 at 415 V?","answer":"Breaking capacity at 415 V is 154 kA. At 240 V it is 220 kA, at 440 V it is 121 kA, and at 690 V it is 17 kA."},{"question":"What are the physical dimensions of 3VA1132-6EF36-0JC0?","answer":"Width is 76.2 mm, height is 130 mm, and depth is 70 mm. Front protection is IP40."},{"question":"Does 3VA1132-6EF36-0JC0 include a shunt trip or undervoltage release?","answer":"It includes a shunt trip (STL) release and 2 auxiliary switches (HQ type). No undervoltage release is fitted on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}