{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 series, molded case circuit breaker, 3VA1132-6EF36-0JH0, 3-pole, 32 A at 40 °C, breaking capacity 220 kA at 240 V AC, line protection design.","salesMarkdown":"It carries a 32 A continuous rating at 40 °C ambient, and the current holds flat through 50 °C — only dropping to 31 A at 55 °C and 30 A at 70 °C, which means you can load it near its nameplate in a warm enclosure without derating panic. The 3-pole construction and 800 V rated insulation voltage suit it for 400 V three-phase mains, and the 220 kA breaking capacity at 240 V handles high-fault utility feeds. The 10.6 W maximum power loss is manageable for a 32 A frame; factor it into your enclosure thermal budget if you're stacking several breakers in a row. The shunt trip lets you remotely open the breaker via a control signal — useful for emergency-stop circuits or interlocking with a fire-alarm panel. The 76.2 mm width (3 inches) is the standard 3-pole MCCB footprint — it occupies one 3-module position in a Siemens SENTRON distribution board. ## Trip indication and design details A trip indicator and a voltage trigger are built in. The trip indicator gives a visible flag when the breaker has opened on fault — useful for a technician walking a row of panels. The voltage trigger enables remote tripping via the shunt release.","metaTitle":"Siemens 3VA1132-6EF36-0JH0 SENTRON MCCB, 32 A, 3-Pole, 70 mm","metaDescription":"Siemens 3VA1132-6EF36-0JH0 SENTRON molded case circuit breaker, 32 A rated at 40 °C, 3-pole, 220 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11326EF360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=80691&mlfb=3VA1132-6EF36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1132-6EF36-0JH0?","answer":"Pricing and availability are confirmed at quote time. Submit an RFQ through this listing; the quote will reflect current distributor stock and market pricing."},{"question":"What is the closest functional second-source to 3VA1132-6EF36-0JH0?","answer":"The 3VA1110-5EF32-0AM0 is a lower-current sibling in the same SENTRON 3VA1 family, but its ratings differ — verify the ampacity and breaking capacity against your application before substituting. The 3VA1132-6EF36-0JH0 carries a 32 A frame; the 3VA1110 variants are typically 10 A or 16 A frames."},{"question":"Will 3VA1132-6EF36-0JH0 drop into a panel specified around 3VA1110-5EF32-0AM0 without rewiring?","answer":"Both are 3-pole SENTRON MCCBs with the same 76.2 mm width and DIN-rail mounting, so the mechanical fit is the same. However, the 3VA1132-6EF36-0JH0 is a 32 A frame versus the 10 A or 16 A frame of the 3VA1110-5EF32-0AM0, so the line and load conductors must be sized for 32 A. If the existing wiring is rated for the lower current, you must rewire."},{"question":"What compliance documentation does Siemens provide for 3VA1132-6EF36-0JH0?","answer":"Siemens provides a declaration of conformity for the SENTRON series covering IEC/EN 60947-2. RoHS and REACH compliance declarations are available from Siemens Industry Online Support. UL listing is standard for the 3VA1 range; verify the specific UL file number against your local code requirement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}