{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6EF36-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6EF36-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, breaking capacity class H, Icu=70kA @ 415V, 3-pole, TM240 line protection, In=32A, overload Ir=22A...32A, shunt trip 220-250V DC / 208-277V AC, 2 auxiliary switches HQ, clamp connection.","salesMarkdown":"## Siemens 3VA1132-6EF36-0KC0 — IEC Frame 160, 70kA Class H The Siemens 3VA1132-6EF36-0KC0 is a 3-pole IEC circuit breaker from the 3VA1 series, built on a 160 A frame with breaking capacity class H — meaning it can interrupt 70 kA at 415 V AC without damage. That Icu rating places it in the high-break category for industrial distribution panels where fault currents are substantial, such as transformer secondaries or motor control center mains. Rated at In=32 A with a TM240 thermal-magnetic trip unit, the overload protection (Ir) is adjustable from 22 A to 32 A, and the instantaneous short-circuit pickup (Ii) is set at 5 to 10 times In. That adjustability lets you coordinate with downstream branch breakers or motor starters without swapping the entire device — useful for panel builders who need selectivity without oversizing. ## Auxiliaries and Trip Accessories The shunt trip allows emergency-off or remote-trip integration into a safety circuit or PLC-driven shutdown sequence. Clamp-type connections simplify panel wiring — no lug crimping needed for the main power terminals.","metaTitle":"Siemens 3VA1132-6EF36-0KC0 Circuit Breaker, 70kA @ 415V, 32A","metaDescription":"Siemens 3VA1132-6EF36-0KC0 IEC 3VA1 circuit breaker, frame 160, breaking capacity class H, Icu=70kA @ 415V, 3-pole, TM240, In=32A. Current lifecycle stage. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=37698&mlfb=3VA1132-6EF36-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6EF36-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"Icu = 70 kA at 415 V AC, placing it in breaking capacity class H for the 3VA1 IEC frame 160 series."},{"question":"Where can I buy 3VA1132-6EF36-0KC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and availability."},{"question":"What does the TM240 trip unit mean?","answer":"TM240 is a thermal-magnetic trip block: overload protection Ir is adjustable 22–32 A, and short-circuit pickup Ii is 5–10× In (160–320 A at the 32 A rating)."},{"question":"Does this breaker include a shunt trip?","answer":"Yes, it comes with a shunt trip (STL) rated for 220–250 V DC or 208–277 V AC, plus two HQ auxiliary switches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6EF36-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6EF36-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}