{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6GF46-0KF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6GF46-0KF0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6GF46-0KF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6GF46-0KF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6GF46-0KF0, molded case circuit breaker, 3-pole, 100 A, TM240 release, 187 kA at 240 V, 121 kA at 415 V.","salesMarkdown":"Interrupting capacity is the headline here: 187 kA at 240 V AC, 121 kA at 415 V, 76 kA at 440 V, and 17 kA at both 500 V and 690 V. Thermal derating is mild: it holds 100 A flat from 40 °C through 50 °C, then drops to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That curve means you don't lose rating in a warm panel until you're past 50 °C ambient — useful when the breaker sits above heat-producing gear in a sealed enclosure. The shunt trip order code is 3VA9688-0BL33 — that's the add-on you need if you're wiring an emergency-stop or remote-trip circuit. For an independent-trader question: this 3VA1132-6GF46-0KF0 will not drop into a panel wired for the 3VA1010-2ED32-0JA0 without checking the mounting footprint and bus-bar spacing — the frame sizes differ (the 3VA1010 is a smaller frame). The auxiliary and shunt-trip wiring may line up, but the physical cutout and lug centers are not guaranteed to match. Best to compare panel cutout dimensions before assuming a swap.","metaTitle":"Siemens 3VA1132-6GF46-0KF0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA1132-6GF46-0KF0 molded case circuit breaker, 100 A rated continuous current, 187 kA interrupting at 240 V. Current production. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"76 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Width [in]":"3 in","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=810436&mlfb=3VA1132-6GF46-0KF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6GF46-0KF0/alternatives.json"},"ai":{"faq":[{"question":"What is the height of this MCCB?","answer":"130 mm, which fits standard SENTRON panelboard mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6GF46-0KF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6GF46-0KF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}