{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-6MH36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-6MH36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-6MH36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6MH36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-6MH36-0AA0, molded case circuit breaker, 3-pole, 32 A, TM120M thermal-magnetic release, 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V.","salesMarkdown":"The interrupting ratings tell the story: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V mean this breaker can clear a fault at those levels without welding contacts or venting gas into the panel. Below 500 V the curve drops to 7.5 kA, and it holds that same 7.5 kA at 690 V — so on a 480 V or 600 V line you're still well within the rating, but the high-fault capability is really in the 240–440 V band where most industrial distribution sits. The TM120M release has an adjustable magnetic trip (li) from 224 A to 510 A — that's 7× to 16× the 32 A continuous rating. For a motor starter circuit you'd set the magnetic pickup just above the inrush so it doesn't nuisance-trip on start, but still catches a locked-rotor fault. The thermal element handles the overload curve; it's fixed at 32 A and derates with ambient temperature — the spec table shows it holds 32 A up to 50 °C, then drops to 31 A at 55–60 °C, and 30 A at 65–70 °C. If your panel runs hot, that 2 A derate matters for the continuous load. Mounting footprint: 76.2 mm wide (3 in), 130 mm tall, 70 mm deep — standard MCCB form factor for a 3-pole frame.","metaTitle":"Siemens 3VA1132-6MH36-0AA0 SENTRON MCCB, 32 A, 220 kA at 240","metaDescription":"Siemens 3VA1132-6MH36-0AA0 SENTRON molded case circuit breaker, 3-pole, 32 A, TM120M release, 220 kA at 240 V. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Number Of Poles":"3","Product version":"Starter protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"32 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM120M","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"510 A","Adjustable response value current / li min.":"224 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=190943&mlfb=3VA1132-6MH36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-6MH36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA1132-6MH36-0AA0?","answer":"3-pole, 32 A continuous (Iu), TM120M thermal-magnetic release with adjustable magnetic trip from 224 A to 510 A. Interrupting: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, 7.5 kA at 500 V and 690 V. Dimensions: 76.2 mm wide, 130 mm high, 70 mm deep."},{"question":"Where can I buy 3VA1132-6MH36-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here."},{"question":"Will 3VA1132-6MH36-0AA0 drop into a panel designed for 3VA1110-5MH36-0AA0?","answer":"Both are 3-pole SENTRON MCCBs in the same 3VA frame family, so the mounting footprint and bus-bar spacing are the same. The 3VA1132 is a higher-interrupting version (220 kA vs lower ratings on the 3VA1110) with a different release curve. If the panel's bus bracing and wire sizing support the higher fault current, it's a direct mechanical swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-6MH36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-6MH36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}