{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1140-4EF32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1140-4EF32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA1140-4EF32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1140-4EF32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1140-4EF32-0AB0, molded case circuit breaker, line protection, 3-pole, 40 A rated continuous current Iu, TM240 thermal-magnetic trip, interrupting capacity 121 kA at 240 V, 75.6 kA at 415 V.","salesMarkdown":"## SENTRON 3VA line protection MCCB — 40 A, high interrupting capacity It carries a rated continuous current Iu of 40 A with a flat thermal derating curve — still rated 40 A at 50 °C, dropping only to 36 A at 70 °C — so it holds its full rating in most ventilated enclosures without oversizing. Interrupting capacity is the headline: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. That 121 kA figure at 240 V puts it well above typical 65 kA or 100 kA MCCBs — useful where fault current is high (large transformer, tight impedance path) and you need to avoid cascading failure upstream. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a compact 3-pole footprint that fits standard Siemens 3VA panel cutouts. Front protection is IP40, so it handles typical panel environments but not washdown. Mounts in a standard SENTRON 3VA panel cutout — 76.2 mm width on a 3-pole footprint. The 70 mm depth leaves clearance for rear busbar connections and wiring troughs. Two auxiliary switches (HP type) are built in for remote status indication; no additional aux block needed for basic open/closed signalling.","metaTitle":"Siemens 3VA1140-4EF32-0AB0 SENTRON MCCB, 40 A, 121 kA at 240","metaDescription":"Siemens SENTRON 3VA1140-4EF32-0AB0 molded case circuit breaker, 40 A rated, TM240 trip, 121 kA at 240 V. Current production. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"40 A","at 45 °C":"40 A","at 50 °C":"40 A","at 55 °C":"38.4 A","at 60 °C":"37.6 A","at 65 °C":"36.8 A","at 70 °C":"36 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"40 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"40 A","Adjustable response value current / li max.":"400 A","Adjustable response value current / li min.":"200 A","Adjustable response value current / lr min.":"28 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=530996&mlfb=3VA1140-4EF32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1140-4EF32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3VA1140-4EF32-0AB0?","answer":"70 mm depth, with a width of 76.2 mm and height of 130 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1140-4EF32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1140-4EF32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}