{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1140-6EE32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1140-6EE32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1140-6EE32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1140-6EE32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, 3-pole circuit breaker, breaking capacity class H, Icu=70kA @ 415V, In=40A, TM220 overload protection, ATFM, nut keeper kit for DC Power OEM in China.","salesMarkdown":"## What this breaker does on the line The Siemens 3VA1140-6EE32-0AA0-ZD00 is a 3-pole IEC frame 160 circuit breaker with a 70 kA breaking capacity at 415 V (class H). Rated In=40 A with adjustable overload protection Ir=28 A…40 A and fixed short-circuit protection Ii=10 × In. The TM220 thermal-magnetic trip gives a 20-second delay at 200% of Ir for motor-start inrush, so it won't nuisance-trip on a pump or compressor start. Mounts on standard DIN rail in an IP40 or higher enclosure. The 3VA1 frame accepts plug-in accessories (auxiliary contacts, shunt trip, undervoltage release) that snap into the side slots without removing the breaker from the rail.","metaTitle":"Siemens 3VA1140-6EE32-0AA0-ZD00 Circuit Breaker, 40A, 70kA @","metaDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, 3-pole, 40A, 70kA breaking capacity @ 415V. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a0496f45852c8df550f9606044a80b44.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667752&mlfb=3VA1140-6EE32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1140-6EE32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1140-6EE32-0AA0-ZD00 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"Icu=70 kA at 415 V (breaking capacity class H), 3-pole. That is the maximum short-circuit current it can safely interrupt at that voltage."},{"question":"What overload protection range does it cover?","answer":"Adjustable overload protection Ir from 28 A to 40 A, with a fixed short-circuit pickup Ii=10 × In (400 A). The TM220 thermal-magnetic trip provides a 20-second delay at 200% of Ir."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1140-6EE32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1140-6EE32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}