{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1140-6EF32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1140-6EF32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1140-6EF32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1140-6EF32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1140-6EF32-0DC0, molded case circuit breaker, 3-pole, 40 A rated continuous current Iu, TM240 thermal-magnetic release, line protection version, 220 kA breaking capacity at 240 V, 70 mm depth, 76.2 mm width, 130 mm height.","salesMarkdown":"Breaking capacity is the headline number for this class: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. The 40 A rating holds flat from 40 °C through 50 °C, then derates to 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C. That's a clean thermal curve — no surprise drop at 40 °C, so if your panel ambient stays under 50 °C you get the full 40 A without headroom padding. ## Panel fit and auxiliary hardware The 3VA1140-6EF32-0DC0 measures 70 mm deep by 76.2 mm wide by 130 mm high. The integrated auxiliary trip order code is 3VA9608-0BB25, which is the factory-fitted accessory you'd order if you need a spare or a replacement sub-assembly. No communication module, no voltage trigger, no phase failure detection, no ground fault monitoring — this is a straight line-protection MCCB. If you need those functions, you step up to the electronic-trip variants in the 3VA family. The rated insulation voltage Ui is 800 V, and the storage temperature range is -40 °C to 80 °C, with an operating range of -25 °C to 70 °C. Latching endurance is rated at 15,000 operations.","metaTitle":"Siemens 3VA1140-6EF32-0DC0 SENTRON MCCB, 40 A, 3-Pole, 220 k","metaDescription":"Siemens SENTRON 3VA1140-6EF32-0DC0 molded case circuit breaker, 40 A rated, 3-pole, line protection. TM240 release, undervoltage release, 2 HQ aux switches. Breaking capacity 220 k","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"40 A","at 45 °C":"40 A","at 50 °C":"40 A","at 55 °C":"38.4 A","at 60 °C":"37.6 A","at 65 °C":"36.8 A","at 70 °C":"36 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"40 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"40 A","Adjustable response value current / li max.":"400 A","Adjustable response value current / li min.":"200 A","Adjustable response value current / lr min.":"28 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=421677&mlfb=3VA1140-6EF32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1140-6EF32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1140-6EF32-0DC0?","answer":"Pricing and availability are confirmed at quote time. Submit an RFQ against this order code; the part is sourced through independent distribution channels and quoted to order."},{"question":"What is the breaking capacity of 3VA1140-6EF32-0DC0 at 240 V?","answer":"The breaking capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V."},{"question":"Does 3VA1140-6EF32-0DC0 include an undervoltage release?","answer":"Yes, it is fitted with an undervoltage release (UVR) as standard, plus 2 HQ auxiliary switches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1140-6EF32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1140-6EF32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}