{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1150-3GD42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1150-3GD42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1150-3GD42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1150-3GD42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1150-3GD42-0AA0, molded case circuit breaker, 50 A fixed, 4-pole, TM210 thermal-magnetic release, 70 mm depth, 101.6 mm width, 130 mm height.","salesMarkdown":"That fixed 50 A holds from 40 °C through 50 °C ambient; above that it derates linearly to 45 A at 70 °C, which matters if this breaker lands in a crowded, hot enclosure without forced cooling. Short-circuit interrupting capacity (SCCR) varies sharply with line voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V or 690 V. The TM210 overcurrent release combines a thermal bimetal for overload protection and a magnetic solenoid for short-circuit response. Maximum power dissipation is 14.6 W — negligible for most panels but worth summing if ten of these sit side-by-side in a sub-distribution board. ## Physical fit — what the 70 mm depth means for the enclosure Width of 101.6 mm (4 inches) is the standard 4-pole MCCB footprint; it mates with the same busbar and lug kits as other SENTRON 3VA 4-pole breakers.","metaTitle":"Siemens 3VA1150-3GD42-0AA0 SENTRON MCCB, 50 A, 4-Pole, TM210","metaDescription":"Siemens SENTRON 3VA1150-3GD42-0AA0 molded case circuit breaker, 50 A fixed, 4-pole, TM210 release. SCCR 75.6 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"50 A","Minimum":"50 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"49 A","at 60 °C":"48 A","at 65 °C":"46 A","at 70 °C":"45 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"14.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/68ee91df20ce4cd90bc8bb8179970cba.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=2822&mlfb=3VA1150-3GD42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1150-3GD42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1150-3GD42-0AA0?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is the interrupting capacity at 415 V?","answer":"The SCCR is 52.5 kA at 415 V."},{"question":"Will 3VA1150-3GD42-0AA0 drop into a panel that was specified around 3VA1110-5ED32-0AA0 without rewiring?","answer":"Both are 4-pole SENTRON 3VA MCCBs with the same 101.6 mm width and 130 mm height, so they share the same mounting footprint and busbar pitch. The 3VA1110-5ED32-0AA0 is a 100 A frame with an electronic release; the 3VA1150-3GD42-0AA0 is a 50 A fixed thermal-magnetic. If the panel busbars and lugs are rated for 50 A, the swap is mechanical — but the trip curve and selectivity coordination must be rechecked."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1150-3GD42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1150-3GD42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}