{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1150-3GD42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1150-3GD42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1150-3GD42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1150-3GD42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 MCCB, breaking capacity class N, 4-pole, TM210 line protection, In=50A, Icu=25kA @ 415V, with N-conductor protection and nut keeper kit.","salesMarkdown":"The Siemens 3VA1150-3GD42-0AA0-ZD00 is a 4-pole molded case circuit breaker (MCCB) on the IEC 3VA1 frame. It is rated for line protection with a TM210 thermal-magnetic trip unit, fixed at In=50A overload protection (Ir=50A) and short-circuit protection set at Ii=10 x In. This variant includes 100% N-conductor protection and a nut keeper kit for DC Power OEM applications in China.","metaTitle":"3VA1150-3GD42-0AA0-ZD00 Siemens 3VA1 MCCB, 50A, 25kA @ 415V,","metaDescription":"Siemens 3VA1150-3GD42-0AA0-ZD00 circuit breaker, IEC frame 160, 50A, 25kA Icu @ 415V, 4-pole, TM210. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/85af0f83b3fab736bb33c980894fb143.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667765&mlfb=3VA1150-3GD42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1150-3GD42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1150-3GD42-0AA0-ZD00 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation."},{"question":"What are the key ratings for 3VA1150-3GD42-0AA0-ZD00?","answer":"It is a 4-pole MCCB with Icu=25kA at 415V, In=50A fixed overload, and Ii=10 x In short-circuit protection. The TM210 trip unit provides line protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1150-3GD42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1150-3GD42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}