{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1150-4EF32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1150-4EF32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1150-4EF32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1150-4EF32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1150-4EF32-0HC0, molded case circuit breaker, 3-pole, 50 A, TM240 release, 121 kA at 240 V, 2 auxiliary switches, shunt trip, IP40 front.","salesMarkdown":"## Breaking capacity — selectivity planning The 3VA1150-4EF32-0HC0: Breaking capacity varies sharply with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. For a 480 V panel, the 52.5 kA figure at 440 V is the closest published value — expect similar or slightly lower at 480 V. ## Panel fit and accessories Footprint is 130 mm high by 76.2 mm wide by 70 mm deep — standard 3-pole MCCB envelope for DIN-rail or screw-mount panel integration.","metaTitle":"Siemens 3VA1150-4EF32-0HC0 SENTRON MCCB, 50 A, 121 kA at 240","metaDescription":"Siemens 3VA1150-4EF32-0HC0 SENTRON molded case circuit breaker, 50 A rated, 121 kA breaking at 240 V. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"48 A","at 60 °C":"47 A","at 65 °C":"46 A","at 70 °C":"45 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"50 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"50 A","Adjustable response value current / li max.":"500 A","Adjustable response value current / li min.":"250 A","Adjustable response value current / lr min.":"35 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=294968&mlfb=3VA1150-4EF32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1150-4EF32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1150-4EF32-0HC0 at 415 V?","answer":"75.6 kA at 415 V, with 52.5 kA at 440 V and 11.9 kA at 690 V."},{"question":"What is the closest functional second-source for 3VA1150-4EF32-0HC0?","answer":"The 3VA1110-5EE32-0JA0 is a peer in the same SENTRON family, but its release and breaking ratings differ — verify the specific trip curve and fault current requirements before substituting."},{"question":"Where can I buy 3VA1150-4EF32-0HC0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1150-4EF32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1150-4EF32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}