{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1150-4EF36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1150-4EF36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1150-4EF36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1150-4EF36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1150-4EF36-0JA0, molded case circuit breaker, 3-pole, 50 A (40 °C), TM240 thermal-magnetic release, shunt trip (STL), line protection, 121 kA at 240 V.","salesMarkdown":"## Siemens 3VA1150-4EF36-0JA0 — 50 A SENTRON MCCB with Shunt Trip It carries a 121 kA interrupting capacity at 240 V, dropping to 75.6 kA at 415 V and 11.9 kA at 690 V — the breaking curve tells you where this breaker is most effective: it handles high fault currents on lower-voltage secondary sides of transformers, not high-voltage motor circuits. Rated uninterrupted current holds at 50 A from 40 °C through 50 °C, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. Maximum power loss is 14.6 W per pole — three poles total about 44 W dissipated inside the enclosure. In a sealed, uncooled panel with multiple breakers, that heat adds up; account for it in the thermal budget. Width 76.2 mm (3 in), height 130 mm (5.12 in), depth 70 mm (2.76 in). Three-pole footprint matches the standard SENTRON 3VA mounting pattern — screws onto the backplate or mounts on a DIN rail adapter (not included).","metaTitle":"Siemens 3VA1150-4EF36-0JA0 SENTRON MCCB, 50 A, 3-Pole, Shunt","metaDescription":"Siemens 3VA1150-4EF36-0JA0 SENTRON molded case circuit breaker, 50 A rated at 40 °C, 3-pole, 121 kA at 240 V. Active production, available to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"49 A","at 60 °C":"48 A","at 65 °C":"46 A","at 70 °C":"45 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"14.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11504EF360AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=464863&mlfb=3VA1150-4EF36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1150-4EF36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA1150-4EF36-0JA0 include a shunt trip?","answer":"Yes, it has a shunt trip (STL) auxiliary release for remote tripping. There is no undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1150-4EF36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1150-4EF36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}