{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1150-6EF32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1150-6EF32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1150-6EF32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1150-6EF32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1150-6EF32-0CH0, molded case circuit breaker, 3-pole, 50 A (rated at 40–50 °C), breaking capacity 220 kA at 240 V AC, with undervoltage release and auxiliary switches.","salesMarkdown":"It's a 3-pole unit rated at 50 A continuous at ambient temperatures up to 50 °C, with a slight derating curve above that — 49 A at 55 °C, 48 A at 60 °C, down to 45 A at 70 °C. That derating matters if you're packing this into a warm enclosure; plan your load accordingly. The interrupting ratings are substantial: 220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. That's a high-fault-current breaker — it'll clear a dead short without upstream coordination headaches in most industrial panels. The 70 mm depth means it clears shallow backpanels without gland-plate interference.","metaTitle":"Siemens 3VA1150-6EF32-0CH0 SENTRON MCCB, 50 A, 3-Pole, 220 k","metaDescription":"Siemens 3VA1150-6EF32-0CH0 SENTRON molded case circuit breaker, 50 A rated, 3-pole, 220 kA breaking capacity at 240 V. Active production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"49 A","at 60 °C":"48 A","at 65 °C":"46 A","at 70 °C":"45 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11506EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=507831&mlfb=3VA1150-6EF32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1150-6EF32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1150-6EF32-0CH0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ and we'll confirm availability and current pricing at quote time."},{"question":"What is the breaking capacity of 3VA1150-6EF32-0CH0 at different voltages?","answer":"The breaker is rated 220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V."},{"question":"Does 3VA1150-6EF32-0CH0 include an undervoltage release?","answer":"Yes, it ships with an integrated undervoltage release (UVR) plus 2 auxiliary switches and a trip alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1150-6EF32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1150-6EF32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}