{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1150-6EF42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1150-6EF42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1150-6EF42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1150-6EF42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class H, Icu=70kA @ 415V, 4-pole, line protection TM240, ATAM, In=50A, overload Ir=35A...50A, short-circuit Ii=5...10 x In.","salesMarkdown":"The Siemens 3VA1150-6EF42-0AA0-ZD00 is a 4-pole IEC frame 160 molded case circuit breaker from the 3VA1 series, configured for line protection with a TM240 thermal-magnetic trip unit. The thermal overload pickup Ir is adjustable from 35 A to 50 A (In=50 A), and the magnetic short-circuit pickup Ii is fixed at 5 to 10 times In. The suffix ZD00 flags a DC Power OEM configuration destined for the China market. The 160 A frame size means the physical footprint, terminal spacing, and busbar drill pattern follow the standard 3VA1 dimensions; it mounts in the same panel cutout as other 3VA1 frame-160 units. The adjustable Ir range (35 to 50 A) lets the breaker be tuned to the actual continuous load, so a single part number covers a spread of motor or feeder ratings within that window.","metaTitle":"Siemens 3VA1150-6EF42-0AA0-ZD00 Circuit Breaker, 70kA @ 415V","metaDescription":"Siemens 3VA1150-6EF42-0AA0-ZD00 IEC frame 160 circuit breaker, 70kA breaking capacity at 415V, 4-pole, In=50A, TM240. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9709477528ff9c5130e563f0d42f6c2c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667791&mlfb=3VA1150-6EF42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1150-6EF42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The breaking capacity is Icu=70kA at 415V, which is the class H rating for the 3VA1 IEC frame 160 platform."},{"question":"Where can I buy the 3VA1150-6EF42-0AA0-ZD00 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What does the TM240 designation mean?","answer":"TM240 refers to the thermal-magnetic trip unit; the thermal element provides overload protection with an adjustable Ir from 35A to 50A, and the magnetic element provides short-circuit protection with a fixed Ii of 5 to 10 times In."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1150-6EF42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1150-6EF42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}