{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-1AA36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-1AA36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-1AA36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-1AA36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 IEC frame 160, 3-pole switch disconnector SD100, In=63 A, without overload or short-circuit protection, clamp connection, shunt trip (STL) 12-30 V DC; 24 V AC 50/60 Hz.","salesMarkdown":"The Siemens SENTRON 3VA1163-1AA36-0HA0 is a 3-pole switch disconnector in the 3VA1 IEC frame-160 platform, rated for 63 A continuous current (Iu) with a maximum AC operating voltage of 690 V at 50/60 Hz and 500 V DC. It is built as a pure disconnect — no overload or short-circuit protection — so it functions as a manual load-break switch for isolating a circuit under load, not as a circuit breaker. The integral shunt trip (STL) release, designed for 12-30 V DC or 24 V AC control, allows remote tripping via a separate signal, which is useful for emergency-stop or supervisory shutdown schemes. The unit measures 70 mm deep by 76.2 mm wide by 130 mm high, which is the standard 3VA1 frame-160 footprint shared across the SENTRON molded-case platform. Front-terminal clamp connections accept copper conductors for the main circuit, so panel wiring is straightforward — no lug crimping required. The 3-pole block occupies three adjacent DIN-rail mounting positions in a typical distribution board. The shunt trip release draws its control power from a separate 12-30 V DC or 24 V AC source — it does not share the main circuit's supply, so the switch can be opened even when the load side is de-energized. There are no auxiliary contacts built in (0 CO contacts), so if status feedback is needed, an external auxiliary switch block must be added via the optional motor-drive accessory slot. ## Environmental limits","metaTitle":"Siemens 3VA1163-1AA36-0HA0 SENTRON Switch Disconnector, 63 A","metaDescription":"Siemens SENTRON 3VA1163-1AA36-0HA0 switch disconnector, 3-pole, 63 A rated continuous current, 690 V AC / 500 V DC max. Shunt trip release. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Limited To 1 S":"2 kA","Trip indicator":"No","Number of poles":"3","Product version":"in MCCB design","Voltage trigger":"Yes","lifecycle_stage":"current","Limited To 0.5 S":"2 kA","Product brand name":"SENTRON","Product designation":"Switch disconnector","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"38 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Number of CO contacts / for auxiliary contacts":"0","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Terminal connection","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=3457&mlfb=3VA1163-1AA36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-1AA36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-1AA36-0HA0 and get a price?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3VA1163-1AA36-0HA0 drop into a panel that was specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"Yes — both share the same 70 mm depth, 76.2 mm width, and 130 mm height, and both use front-terminal connections. The footprint is identical, so it fits the same panel cutout and DIN-rail mounting. The difference is functional: the 3VA1110-5EE32-0JA0 is a molded-case circuit breaker with overcurrent protection, while this part is a switch disconnector with no overload or short-circuit protection. The wiring lands the same way, but the circuit protection must be provided elsewhere."},{"question":"What compliance documentation does this brand provide for 3VA1163-1AA36-0HA0?","answer":"As a Siemens SENTRON product, it is designed to meet IEC/EN 60947-3 for switch-disconnectors and carries CE marking for the European market. RoHS and REACH compliance documentation is typically included with the product or available from the manufacturer's support portal. The IP40 front-face rating is per IEC 60529."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-1AA36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-1AA36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}