{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-3EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-3EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-3EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-3EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1163-3EE32-0AA0, Molded case circuit breaker, 3-pole, 63 A at 40 °C, TM220 overcurrent release, 75.6 kA breaking capacity at 240 V, line protection design, IP40 front, 70 mm depth.","salesMarkdown":"Breaking capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — enough for most industrial secondary distribution, but check your available fault current at the point of installation. Three-pole, 70 mm deep, 76.2 mm wide, 130 mm tall — standard MCCB footprint for a 3-pole 63 A frame, bolts into a distribution panel or mounts on a mounting plate. Marked as current-production lifecycle stage — this is not an NRND or obsolete line; Siemens continues to manufacture the 3VA series. No official successor order code exists because the part is still active. ## What the TM220 release means on the line No electronic trip unit, no communication, no ground-fault monitoring built in. Max power loss 17.3 W at rated load — negligible for panel heat budget, but worth noting if you're stacking a dozen of these in a sealed enclosure.","metaTitle":"Siemens 3VA1163-3EE32-0AA0 SENTRON MCCB, 63 A, 3-Pole, 75.6","metaDescription":"Siemens 3VA1163-3EE32-0AA0 SENTRON molded case circuit breaker, 63 A rated at 40 °C, 3-pole, 75.6 kA breaking at 240 V. TM220 release, line protection. Sourced to order against RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1163-3EE32-0AA0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class N Icu=25kA @ 415V 3-pole, line protection TM220, ATFM, In=63A overload protection Ir=44A...63A short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4fb06c49d5111f77b7cd926a755122d3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=397201&mlfb=3VA1163-3EE32-0AA0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1163-3EE32-0AA0?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution; pricing and stock levels are confirmed at quote time, not displayed as a static number."},{"question":"What is the breaking capacity of 3VA1163-3EE32-0AA0 at 240 V?","answer":"75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a SENTRON series MCCB, it carries UL, CSA, and IEC certifications typical for the 3VA family. Specific RoHS and REACH declarations are available in the product documentation linked from the Siemens support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-3EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-3EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}