{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-4ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-4ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-4ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-4ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 series, molded case circuit breaker (MCCB), 2-pole, 63 A rated at 40 °C, TM210 thermal-magnetic trip, 121 kA breaking capacity at 240 VAC, IP40 front protection.","salesMarkdown":"## Siemens 3VA1163-4ED22-0AA0 — 63 A SENTRON MCCB, 2-Pole, TM210 Trip It carries a 121 kA interrupting capacity at 240 VAC and 75.6 kA at 415 VAC, giving it substantial fault-current headroom for high-available-fault service entrances or sub-distribution boards. The TM210 thermal-magnetic trip unit provides fixed thermal and magnetic settings — no field-adjustable dials — so the coordination study needs to lock in the 63 A frame before ordering. Maximum power loss at rated load is 11.54 W, a figure to include in the panel thermal budget if the enclosure is tightly packed. Dimensions are 130 mm height, 70 mm depth, and 50.8 mm width — a 2-inch-wide footprint that fits standard 2-pole MCCB panel cutouts. No undervoltage release, no shunt trip, and no communication function are built in; if remote tripping or status feedback is needed, order the accessory modules separately.","metaTitle":"Siemens 3VA1163-4ED22-0AA0 SENTRON MCCB, 63 A, 2-Pole, TM210","metaDescription":"Siemens 3VA1163-4ED22-0AA0 SENTRON molded case circuit breaker, 63 A rated at 40 °C, 2-pole, TM210 thermal-magnetic trip, 121 kA at 240 VAC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"11.54 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e6f4558e654a02e4835445d6fe31b780.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=505375&mlfb=3VA1163-4ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-4ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB?","answer":"121 kA at 240 VAC and 75.6 kA at 415 VAC. These are high-interrupting ratings suitable for service-entrance or main-switchboard positions with high available fault current."},{"question":"What trip unit does the 3VA1163-4ED22-0AA0 use?","answer":"It uses a TM210 thermal-magnetic trip unit — fixed thermal and magnetic settings, no field adjustment. The 63 A rating is set at the factory."},{"question":"Where can I buy the 3VA1163-4ED22-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial automation distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-4ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-4ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}