{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-4EF36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-4EF36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-4EF36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-4EF36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 molded case circuit breaker, 3-pole, 63 A rated current at 40 °C, 121 kA breaking capacity at 240 V, TM240 overcurrent release, shunt trip, line protection.","salesMarkdown":"It carries a rated current of 63 A at 40 °C and holds that rating through 50 °C before a slight thermal derating curve begins — at 55 °C it's still 62 A, at 65 °C it's 60 A, and at 70 °C it's 58 A, so the full 63 A is usable across most normal panel ambient conditions. The breaking capacity is the headline number that decides fault-clearing fit: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that drops into most DIN-rail or panel-mount enclosures without surprises. The 63 A rating at 40 °C with minimal derating up to 50 °C means this breaker handles continuous loads like lighting panels, small distribution feeders, or motor branch circuits without needing oversizing for ambient temperature. Compared to a lower-rated sibling like the 3VA1110-5EF32-0LA0 (which carries a lower current frame), this 3VA1163-4EF36-0HA0 is the higher-current, higher-breaking-capacity option in the 3VA1 family. The physical footprint is the same 3-pole width, so a panel designed for the smaller frame can accept this one without re-drilling or busbar rework — the mounting and connection pattern is consistent across the 3VA1 line.","metaTitle":"Siemens 3VA1163-4EF36-0HA0 SENTRON MCCB, 63 A, 121 kA at 240","metaDescription":"Siemens 3VA1163-4EF36-0HA0 SENTRON molded case circuit breaker, 3-pole, 63 A rated at 40 °C, 121 kA breaking capacity at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11634EF360AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=156888&mlfb=3VA1163-4EF36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-4EF36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What type of overcurrent release does this MCCB have?","answer":"It has a TM240 thermal-magnetic overcurrent release, plus a shunt trip (STL) auxiliary release for remote tripping. The rated insulation voltage is 800 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-4EF36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-4EF36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}