{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-5ED32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-5ED32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-5ED32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1163-5ED32-0DA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 187 kA breaking capacity at 240 V, TM210 overcurrent release, undervoltage release, IP40 front.","salesMarkdown":"It carries 63 A continuous current (Iu) at 40 °C through 50 °C, then derates to 60.48 A at 55 °C and 56.7 A at 70 °C — so in a warm panel you lose about 10 % of the headline number. The TM210 thermal-magnetic overcurrent release handles the overload and short-circuit trip curve; there is no electronic trip unit, no communication module, and no phase-failure detection built in. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — figures that cover most industrial distribution boards fed from a transformer of moderate impedance. An undervoltage release (UVR) is fitted as standard (design code 3VA9608-0BB25 for the integrated auxiliary trip), but there is no auxiliary contact block on this variant. The 3VA1163-5ED32-0DA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. That 76.2 mm width (three modules at roughly 25.4 mm per pole) is the standard SENTRON 3VA fixed-format footprint — it clips onto the DIN rail and occupies the same slot as any other 3-pole 3VA frame. If you are swapping out an older 3VF or 3VL series breaker, check the busbar pitch: the 3VA line uses the same 60 mm centre-to-centre spacing on the load terminals, so a direct mechanical swap is likely, but verify the terminal lug type (box lug vs. ring-tongue) before committing the BOM. It remains an active catalogue line within the SENTRON 3VA family. No official successor has been published, so this is the direct drop-in for any panel originally specified with this code. ## Storage and operating limits","metaTitle":"Siemens 3VA1163-5ED32-0DA0 MCCB, 63 A, 187 kA at 240 V","metaDescription":"Siemens SENTRON 3VA1163-5ED32-0DA0 molded case circuit breaker, 63 A rated continuous current, 187 kA breaking capacity at 240 V. Current lifecycle stage. Quoted to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=16756&mlfb=3VA1163-5ED32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED32-0DA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-5ED32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-5ED32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}