{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-5ED32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-5ED32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-5ED32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1163-5ED32-0JC0, molded case circuit breaker, 3-pole, 63 A, line protection, TM210 thermal-magnetic release, 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 17 kA at 690 V.","salesMarkdown":"The Siemens SENTRON 3VA1163-5ED32-0JC0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release and a shunt trip (STL) auxiliary release. Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — figures that govern selectivity and SCCR coordination in a distribution panel. Above that, the TM210 release begins to derate: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. ## Integration and auxiliary options No undervoltage release, ground-fault monitoring, phase-failure detection, or communication module is fitted on this variant — those are separate add-on options in the SENTRON accessory range. For DC network applications, the manufacturer directs to the 3VA molded case circuit breaker device manual for specific switching power values.","metaTitle":"Siemens 3VA1163-5ED32-0JC0 SENTRON MCCB, 63 A, 187 kA at 240","metaDescription":"Siemens SENTRON 3VA1163-5ED32-0JC0 molded case circuit breaker, 63 A, 3-pole, line protection, TM210 release, 187 kA at 240 V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=163459&mlfb=3VA1163-5ED32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1163-5ED32-0JC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm response."},{"question":"What is the interrupting capacity of 3VA1163-5ED32-0JC0 at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. These ratings determine selectivity and SCCR coordination in the distribution panel."},{"question":"Does 3VA1163-5ED32-0JC0 include a shunt trip or undervoltage release?","answer":"It includes a shunt trip (STL) auxiliary release. No undervoltage release is fitted on this variant."},{"question":"What is the closest functional alternative to 3VA1163-5ED32-0JC0?","answer":"The 3VA1010-2ED32-0JA0 is a lower-current sibling in the same SENTRON 3VA family. It shares the same 3-pole, line-protection, TM210 release architecture but at a lower continuous current rating. Panel cutout and mounting are identical, so it drops into the same footprint without rewiring, but the interrupting capacity and thermal ratings differ — verify the load current before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-5ED32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-5ED32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}