{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-5ED32-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-5ED32-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-5ED32-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED32-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1163-5ED32-0KA0, molded case circuit breaker, 3-pole, 63 A rated current at 40 °C, TM210 thermal-magnetic release, shunt trip (STL), 187 kA breaking capacity at 240 V.","salesMarkdown":"The 63 A rating holds flat from 40 °C through 50 °C, then derates to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. Breaking capacity drops with voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V. ## Integration notes Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. The shunt trip (STL) allows remote opening via a control signal, useful for emergency-stop circuits or automated load shedding.","metaTitle":"Siemens 3VA1163-5ED32-0KA0 SENTRON MCCB, 63 A, 3-Pole, 187 k","metaDescription":"Siemens SENTRON 3VA1163-5ED32-0KA0 molded case circuit breaker, 63 A at 40 °C, 3-pole, 187 kA breaking capacity at 240 V. TM210 release, shunt trip. Active production. Quoted to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11635ED320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=427830&mlfb=3VA1163-5ED32-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED32-0KA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1163-5ED32-0KA0 at 480 V?","answer":"At 440 V it is rated 75.6 kA; at 500 V it drops to 17 kA. For a 480 V system, the 440 V figure (75.6 kA) is the closest published rating — use that for coordination studies."},{"question":"Where can I buy 3VA1163-5ED32-0KA0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3VA1163-5ED32-0KA0 drop into a panel specified around 3VA1110-5ED36-0AC0?","answer":"Both are 3-pole SENTRON 3VA MCCBs with the same 130 mm height, 76.2 mm width, and 70 mm depth footprint, so they share the same mounting hole pattern and bus-bar spacing. The 3VA1110-5ED36-0AC0 is a different amp rating and release variant — verify the load current and trip curve before substitution."},{"question":"What compliance documentation does Siemens provide for 3VA1163-5ED32-0KA0?","answer":"As a current-production SENTRON MCCB, it carries CE marking for the European market and is designed to meet IEC 60947-2. UL/CSA listings are typical for the 3VA platform, but specific certification markings on this order code should be verified against the nameplate or Siemens declaration of conformity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-5ED32-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-5ED32-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}