{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-5ED46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-5ED46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-5ED46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1163-5ED46-0AA0, molded case circuit breaker, line protection, 4-pole, 63 A, TM210 thermal-magnetic release, breaking capacity 187 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA1163-5ED46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 63 A at 40 °C through 50 °C before derating begins — at 70 °C it still holds 58 A. This MCCB interrupts 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The breaker measures 101.6 mm wide, 130 mm high, and 70 mm deep — a standard SENTRON 3VA frame footprint that drops into existing DIN-rail or panel-mount layouts without re-drilling. The 4-pole configuration covers three-phase plus neutral, common for TT or TN-S systems where the neutral needs overcurrent protection. ## What the TM210 release and power loss tell you The TM210 designation means a thermal-magnetic release with a fixed thermal pickup and adjustable magnetic trip — the '210' typically indicates the magnetic trip is set at 10x In (630 A), so it's a standard motor-and-distribution profile, not a selective or high-inrush variant. An optional motor drive extension is available for remote switching.","metaTitle":"Siemens 3VA1163-5ED46-0AA0 SENTRON MCCB, 63 A, 4-Pole, 187 k","metaDescription":"Siemens SENTRON 3VA1163-5ED46-0AA0 molded case circuit breaker, 63 A continuous, 4-pole, TM210 release. Breaking capacity 187 kA at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"63 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"600 V","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/13f250860637437b9a6411d9849ceaed.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=446268&mlfb=3VA1163-5ED46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5ED46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-5ED46-0AA0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest lead time."},{"question":"What is the breaking capacity of 3VA1163-5ED46-0AA0 at 415 V?","answer":"It interrupts 121 kA at 415 V, which is the maximum fault current it can safely clear at that voltage level."},{"question":"Will 3VA1163-5ED46-0AA0 fit in a panel designed for 3VA1110-5ED36-0AA0?","answer":"Both are 3VA frame breakers with the same 101.6 mm width, 130 mm height, and 70 mm depth, so the physical footprint is identical — no rewiring or re-drilling needed for the panel cutout. Verify the terminal arrangement and accessory compatibility against your specific wiring plan."},{"question":"What compliance documentation is available for this MCCB?","answer":"As a Siemens SENTRON product, it carries CE marking for the European market and is designed to meet IEC 60947-2. RoHS and REACH declarations are standard from the manufacturer. For specific UL or CSA documentation, confirm with the order code suffix — this variant's documentation set should be verified at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-5ED46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-5ED46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}