{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-5EE32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-5EE32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-5EE32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5EE32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class M, 3-pole, 63A, Icu=55kA @ 415V, line protection TM220, ATFM, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1163-5EE32-0AA0-ZD00 is a 3-pole IEC frame 160 molded case circuit breaker rated 63 A with a breaking capacity class M, delivering Icu=55 kA at 415 V. It carries line protection via a TM220 thermal-magnetic trip unit with ATFM (adjustable thermal, fixed magnetic) — overload protection Ir adjustable from 44 A to 63 A, short-circuit protection Ii fixed at 10 x In. The suffix ZD00 indicates a nut keeper kit included, configured for a DC Power OEM in China. For most industrial distribution panels fed from a transformer of 1000 kVA or less, that's enough headroom to avoid cascading upstream. The 63 A frame with adjustable thermal pickup (44–63 A) lets you match the cable or load without swapping the breaker body. Fixed magnetic Ii at 10 x In (630 A) means it holds through motor inrush on a 63 A feeder but trips fast on a bolted fault.","metaTitle":"Siemens 3VA1163-5EE32-0AA0-ZD00 Circuit Breaker, 63A, 55kA @","metaDescription":"Siemens 3VA1163-5EE32-0AA0-ZD00 IEC frame 160 MCCB, 3-pole, 63A, 55kA breaking capacity @ 415V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ab8cef24a6df7e91e40b5deffd507850.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667815&mlfb=3VA1163-5EE32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5EE32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-5EE32-0AA0-ZD00 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings for this circuit breaker?","answer":"It is a 3-pole IEC frame 160 MCCB rated 63 A with Icu=55 kA at 415 V. Overload protection Ir is adjustable 44–63 A; short-circuit protection Ii is fixed at 10 x In (630 A)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-5EE32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-5EE32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}