{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-5MH36-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-5MH36-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-5MH36-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5MH36-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, molded case circuit breaker, 3VA1163-5MH36-0HH0, 3-pole, 63 A at 40 °C, breaking capacity 187 kA at 240 V, starter protection design, shunt trip release, 70 mm depth.","salesMarkdown":"## MCCB for motor and starter protection It's a 3-pole unit rated 63 A continuously at 40 °C, with a thermal derating curve that holds 63 A up to 50 °C, then drops to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. That's a shallow derating slope, so you don't lose much headroom in a warm panel. Breaking capacity is the headline: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. At 415 V you're well above typical 50 kA utility fault levels, so this breaker gives selectivity headroom without cascading upstream. At 690 V the 7.5 kA limit is the constraint — verify your available fault current if the line runs at that voltage. Max power loss is 17.3 W, which matters for panel thermal calculations in a sealed enclosure. The supplied basic switch is 3VA11635MH360AA0.","metaTitle":"Siemens 3VA1163-5MH36-0HH0 SENTRON MCCB, 63 A, 3-Pole, 70 mm","metaDescription":"Siemens 3VA1163-5MH36-0HH0 SENTRON molded case circuit breaker, 63 A at 40 °C, 3-pole, breaking capacity 187 kA at 240 V. Starter protection design with shunt trip. Available to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Starter protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11635MH360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM120M","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=164999&mlfb=3VA1163-5MH36-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-5MH36-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"Breaking capacity is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V."},{"question":"Where can I buy 3VA1163-5MH36-0HH0 and how is it quoted?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — volume pricing is confirmed at quote time based on your quantity and delivery requirements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-5MH36-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-5MH36-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}