{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-6ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-6ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-6ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1, molded case circuit breaker, 3-pole, 63 A (40 °C), TM210 thermal-magnetic release, line protection, breaking capacity 220 kA at 240 V AC.","salesMarkdown":"It carries a continuous 63 A at 40 °C (derated to 58 A at 70 °C) across three poles, with a TM210 thermal-magnetic release that handles overload and short-circuit tripping without external control power. Breaking capacity is the headline here: 220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and still 17 kA at 690 V. At 690 V the 17 kA still covers most industrial motor-circuit fault levels. For a site electrical engineer working through a coordination study: the 63 A frame with 220 kA SCCR at 240 V gives you headroom to cascade downstream breakers with lower interrupting ratings, provided the let-through energy (I²t) of this MCCB is below the withstand of the downstream devices. Siemens publishes energy let-through curves for the 3VA1 series — use those, not generic assumptions, for the series-rating tables. The TM210 release is fixed thermal and fixed magnetic — no interchangeable trip units, no electronic adjustment. That simplifies spares but locks you into the 63 A rating. If the load grows, you replace the breaker, not the trip. The 76.2 mm width occupies three pole positions on a DIN rail. Power dissipation at rated current is 17.3 W maximum — negligible for panel thermal calculations but worth noting if the enclosure is densely packed.","metaTitle":"Siemens 3VA1163-6ED32-0AA0 SENTRON MCCB, 63 A, 3-Pole, 220 k","metaDescription":"Siemens 3VA1163-6ED32-0AA0 SENTRON molded case circuit breaker, 63 A rated, 3-pole, 220 kA breaking capacity at 240 V. TM210 release. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e6c3f9c3cb8c070f462aa2b821f7a3a0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=227157&mlfb=3VA1163-6ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6ED32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA1163-6ED32-0AA0 have a communication module or ground-fault monitoring?","answer":"No. This variant has no communication function, no ground-fault monitoring, and no undervoltage release. It is a straight thermal-magnetic breaker with a TM210 release for line protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-6ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-6ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}