{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-6ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-6ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-6ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, 3-pole circuit breaker, 63 A, breaking capacity class H Icu=70 kA @ 415 V, TM210 line protection, nut keeper kit for DC Power OEM.","salesMarkdown":"It is a 3-pole unit rated at 63 A (In), with a fixed overload protection setting (Ir = 63 A) and a fixed short-circuit protection setting (Ii = 10 × In). The nut keeper kit (ZD00 suffix) ships in the carton — no separate bracket order needed, so the kit is complete for the OEM install. The TM210 trip unit is fixed, not adjustable for overload; the short-circuit pickup is fixed at 10× In, so verify coordination with downstream devices before committing the BOM line.","metaTitle":"Siemens 3VA1163-6ED32-0AA0-ZD00 Circuit Breaker, 63A, 70kA @","metaDescription":"Siemens 3VA1163-6ED32-0AA0-ZD00 IEC frame 160 breaker, 3-pole, 63A, 70kA breaking capacity @ 415V. Current production. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b5c38d506220c75d13e66c1463d1aee7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667822&mlfb=3VA1163-6ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-6ED32-0AA0-ZD00 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"The breaking capacity is class H, rated Icu = 70 kA at 415 V, meaning it safely interrupts fault currents up to that level."},{"question":"What does the ZD00 suffix indicate?","answer":"The ZD00 suffix indicates a nut keeper kit for DC Power OEM applications — the accessory ships with the breaker, so the kit is complete for that install."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-6ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-6ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}