{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-6EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-6EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-6EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1163-6EE32-0AA0, 3-pole molded case circuit breaker, 63 A continuous, TM220 thermal-magnetic release, 220 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA1163-6EE32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 63 A continuous current (Iu) at up to 40 °C with no derating — it holds 63 A through 50 °C, then drops to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. The interrupting capacity tells the real story: 220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, then stepping to 17 kA at both 500 V and 690 V. ## Integration and footprint","metaTitle":"Siemens 3VA1163-6EE32-0AA0 SENTRON MCCB, 63 A, 220 kA at 240","metaDescription":"Siemens SENTRON 3VA1163-6EE32-0AA0 molded case circuit breaker, 3-pole, 63 A, TM220 release, 220 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"63 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","reference value setting current (Ii) / for I-tripping":"x In","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","type of value list setting current (Ii) / for I-tripping":"Fest","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6,5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=139863&mlfb=3VA1163-6EE32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6EE32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-6EE32-0AA0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA1163-6EE32-0AA0 at different voltages?","answer":"220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V."},{"question":"What type of overcurrent release does 3VA1163-6EE32-0AA0 use?","answer":"TM220 thermal-magnetic release — fixed thermal and magnetic trip settings, no electronic adjustments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-6EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-6EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}