{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-6EE32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-6EE32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-6EE32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6EE32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, 3-pole, breaking capacity class H, Icu=70kA @ 415V, TM220 thermal-magnetic trip, In=63A, overload Ir=44A...63A, short-circuit Ii=10 x In, with nut keeper kit for DC Power OEM in China.","salesMarkdown":"## What this 3VA1 breaker carries The Siemens 3VA1163-6EE32-0AA0-ZD00 is a 3-pole IEC frame 160 circuit breaker in breaking capacity class H, rated to interrupt 70 kA at 415 V. Overload protection uses a TM220 thermal-magnetic trip unit, adjustable from 44 A to 63 A via the Ir dial. Short-circuit pickup is fixed at 10 x In (630 A magnetic). For a 63 A feeder feeding a motor control center or a distribution sub-panel, that's a standard coordination curve — the magnetic floor keeps nuisance trips off during inrush while still clearing a bolted fault fast. The suffix ZD00 indicates this variant includes a nut keeper kit and is configured for a DC Power OEM in China. That's a factory-customized order code — the base electrical ratings (frame, poles, breaking capacity, trip) are standard 3VA1, but the accessory kit and OEM designation mean you're buying the exact BOM-listed variant, not a parametric substitute. At 3-pole with a 63 A TM220 trip, it occupies the same panel footprint as any 3VA1 frame breaker — so if you're replacing a failed unit or adding a feeder, the busbar and lug kit spacing is standard for the series. That gives you headroom for high-fault installations (close to a transformer secondary or a large generator bus) without needing a current-limiting upstream breaker.","metaTitle":"Siemens 3VA1163-6EE32-0AA0-ZD00 Circuit Breaker, 70kA @ 415V","metaDescription":"Siemens 3VA1163-6EE32-0AA0-ZD00 IEC frame 160 circuit breaker, 70kA breaking capacity @ 415V, 63A TM220 overload protection. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/933cbb97101475d7f5d041cd8b3b2bef.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667824&mlfb=3VA1163-6EE32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6EE32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-6EE32-0AA0-ZD00 and what is the lead time?","answer":"This OEM-specific variant is sourced to order through our independent distribution network. Submit an RFQ for current pricing and lead time — availability is confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"It is rated Icu = 70 kA at 415 V, breaking capacity class H on the 3VA1 IEC frame."},{"question":"What are the overload and short-circuit protection settings?","answer":"Overload protection Ir is adjustable from 44 A to 63 A via the TM220 thermal-magnetic trip. Short-circuit protection Ii is fixed at 10 x In (630 A magnetic)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-6EE32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-6EE32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}