{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-6GD46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-6GD46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-6GD46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6GD46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1163-6GD46-0AA0, 4-pole molded case circuit breaker, 63 A rated current, TM210 overcurrent release, interrupting capacity 220 kA at 240 V.","salesMarkdown":"## What this 63 A MCCB delivers The Siemens SENTRON 3VA1163-6GD46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated at 63 A continuous — the same figure at 40 °C, 45 °C, and 50 °C, then derating to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. That flat thermal curve means you can load it to 63 A in most panel environments without headroom padding. Interrupting capacity hits 220 kA at 240 V, drops to 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. The TM210 overcurrent release handles the thermal-magnetic trip curve — no electronic trip unit, no communication function, no voltage trigger or undervoltage release on this variant. Footprint is 101.6 mm wide by 130 mm tall by 70 mm deep — a standard 4-pole MCCB width that slots into SENTRON panelboards and distribution blocks without adaptor plates.","metaTitle":"Siemens SENTRON 3VA1163-6GD46-0AA0 4-Pole MCCB, 63 A, 220 kA","metaDescription":"Siemens SENTRON 3VA1163-6GD46-0AA0 4-pole molded case circuit breaker, 63 A rated, TM210 release. Interrupting capacity 220 kA at 240 V. Current lifecycle. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"63 A","Minimum":"63 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=376361&mlfb=3VA1163-6GD46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6GD46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-6GD46-0AA0 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and target delivery window."},{"question":"What is the interrupting capacity of this MCCB at different voltages?","answer":"220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V — the high-end short-circuit rating at 240 V suits it for transformer-secondary or generator-fed applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-6GD46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-6GD46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}