{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1163-6MH36-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1163-6MH36-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA1163-6MH36-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6MH36-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, 3-pole, breaking capacity class H (Icu=70kA @ 415V), starter protection TM120M, AM, In=63A, without overload protection, short-circuit protection Ii=5...15 x In, clamp connection, 4 auxiliary switches HQ.","salesMarkdown":"The Siemens 3VA1163-6MH36-0AE0 is a 3-pole IEC frame 160 circuit breaker with a 63 A rated current and a 70 kA breaking capacity at 415 V (class H). The TM120M trip unit provides starter protection (motor-starting duty), but note this variant ships without overload protection: the TM120M handles short-circuit only (Ii adjustable 5...15 x In). You'll need a separate overload relay upstream if the load is a motor. Clamp-type terminals accept standard copper conductors; no lugs required for panel wiring. ## Deployment context The clamp terminals and compact 3VA1 footprint simplify panel integration; the four auxiliary switches reduce the need for separate contact blocks.","metaTitle":"Siemens 3VA1163-6MH36-0AE0 Circuit Breaker, 63A, 70kA @ 415V","metaDescription":"Siemens 3VA1163-6MH36-0AE0 IEC frame 160 circuit breaker, 63A, 70kA breaking capacity at 415V, 3-pole, starter protection TM120M, current lifecycle stage. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=461422&mlfb=3VA1163-6MH36-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1163-6MH36-0AE0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1163-6MH36-0AE0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"The rated ultimate breaking capacity (Icu) is 70 kA at 415 V AC, class H per IEC 60947-2."},{"question":"Does this breaker include overload protection?","answer":"No — the TM120M trip unit provides short-circuit protection only (adjustable Ii = 5...15 x In). A separate overload relay is required for motor overload protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1163-6MH36-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1163-6MH36-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}