{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-3ED16-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-3ED16-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-3ED16-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-3ED16-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker (MCCB), 3VA1180-3ED16-0AA0, 1-pole, 80 A rated continuous current, 25.4 mm width, TM210 thermal-magnetic release.","salesMarkdown":"It carries a 52.5 kA interrupting capacity at 240 V AC and 7.5 kA at 415 V AC — the 240 V figure is the one that governs most North American panel schedules. At 25.4 mm wide on a 70 mm depth, it fits a standard DIN-rail footprint; the 130 mm height leaves headroom for auxiliary modules above it in the enclosure. Above that it steps down: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, 74 A at 70 °C. Maximum power loss is 6.4 W, negligible for most DIN-rail layouts but worth a glance if the breaker shares a small gland plate with other heat sources. ## Integration notes IP40 on the front face — suitable for dry indoor panels, not washdown zones. The 500 V rated insulation voltage covers 480 V delta systems with margin. Width of 25.4 mm (1 inch) means it occupies one standard pole position on the DIN rail; plan your fill factor accordingly.","metaTitle":"Siemens 3VA1180-3ED16-0AA0 SENTRON MCCB, 80 A, 1-Pole, 25.4","metaDescription":"Siemens SENTRON 3VA1180-3ED16-0AA0 molded case circuit breaker, 80 A continuous, 1-pole, 25.4 mm wide, 52.5 kA at 240 V. Active production. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"25.4 mm","Height":"130 mm","Maximum":"800 A","Minimum":"800 A","at 240 V":"52.5 kA","at 415 V":"7.5 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"1 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"1","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"6.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"80 A","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"125 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1493a0373807aee4566c21b271047bd8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=129983&mlfb=3VA1180-3ED16-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-3ED16-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1180-3ED16-0AA0?","answer":"Submit an RFQ against this order code. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is the closest functional second-source for 3VA1180-3ED16-0AA0?","answer":"Within the same SENTRON 3VA family, the 3VA1110-5ED36-0AA0 is a 1-pole 80 A MCCB with a TM210 release. The key difference is the 3VA1110 frame carries different breaking capacities and accessory compatibility — verify the interrupting rating at your fault level before substituting."},{"question":"What is the width of 3VA1180-3ED16-0AA0?","answer":"25.4 mm (1 inch) wide — one standard DIN-rail pole position."},{"question":"What compliance documentation does this breaker carry?","answer":"The SENTRON 3VA series is designed to meet IEC 60947-2 and UL 489 standards. Specific declarations (CE, UKCA, EAC, RoHS, REACH) are issued per manufacturing batch; request the compliance pack with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-3ED16-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-3ED16-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}