{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-3ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-3ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-3ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-3ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 MCCB, 3-pole, breaking capacity class N, 25kA Icu @ 415V, fixed thermal-magnetic TM210 trip, 80A, nut keeper kit for DC Power OEM in China.","salesMarkdown":"It carries a fixed 80 A thermal-magnetic trip unit (TM210) with overload protection set at Ir = 80 A and fixed short-circuit protection at Ii = 10 × In (800 A). The Ii = 10 × In (800 A) short-circuit pickup is also fixed, typical for TM210 trip units. Verify the load's full-load amps match 80 A before specifying. The nut keeper kit is a mechanical detail for the DC Power OEM variant — it retains the terminal nuts during high-vibration transport or operation.","metaTitle":"Siemens 3VA1180-3ED32-0AA0-ZD00 Circuit Breaker, 80A, 25kA @","metaDescription":"Siemens 3VA1180-3ED32-0AA0-ZD00 IEC frame 160 MCCB, 3-pole, 80A fixed thermal-magnetic, 25kA Icu @ 415V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bce5851d10b5e1bf55cc868302e9d6c5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667831&mlfb=3VA1180-3ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-3ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1180-3ED32-0AA0-ZD00 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings for this MCCB?","answer":"The 3VA1180-3ED32-0AA0-ZD00 is a 3-pole IEC frame 160 MCCB with 80 A fixed thermal-magnetic trip (TM210), breaking capacity class N (25 kA Icu @ 415 V), and fixed short-circuit protection set at 10 × In (800 A)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-3ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-3ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}