{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-3ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-3ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-3ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-3ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1180-3ED36-0AA0, molded case circuit breaker, 3-pole, 80 A, breaking capacity 75.6 kA at 240 V AC, TM210 release, line protection.","salesMarkdown":"Its TM210 thermal-magnetic release provides overload and short-circuit protection for cable and busbar feeders. The 80 A rating holds steady from 40 °C through 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. Breaking capacity drops with voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V. The 3-pole width (76.2 mm) is standard for a 160 A frame MCCB — fits a typical 3-module cutout in a Siemens SENTRON distribution panel or any DIN-rail adapter plate. Rated insulation voltage 800 V, power loss 19.2 W maximum. That heat must be vented — allow free air circulation around the breaker; do not bury it behind tightly packed wiring ducts.","metaTitle":"Siemens 3VA1180-3ED36-0AA0 SENTRON MCCB, 80A, 3-Pole, 75.6kA","metaDescription":"Siemens SENTRON 3VA1180-3ED36-0AA0 molded case circuit breaker, 80A, 3-pole, 75.6kA at 240V. Active production. Sourced to order against RFQ. IP40 front.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.2 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b9a90c0b571dd8876dd663a683cf5489.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=284158&mlfb=3VA1180-3ED36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-3ED36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1180-3ED36-0AA0 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution with full traceability. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What is the breaking capacity of 3VA1180-3ED36-0AA0 at different voltages?","answer":"75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. The 11.9 kA figure at 500 V is the closest reference for 480 V panels."},{"question":"What does the TM210 release designation mean on this MCCB?","answer":"TM210 indicates a thermal-magnetic release — the thermal element handles overload protection (inverse time curve), and the magnetic element handles instantaneous short-circuit protection. It is the standard release for line protection, not adjustable electronic trip."},{"question":"Does 3VA1180-3ED36-0AA0 have a communication function or ground-fault monitoring?","answer":"No. This breaker has no communication function and no ground-fault monitoring version. It is a basic thermal-magnetic MCCB for line protection — no aux contacts, shunt trip, or electronic trip unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-3ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-3ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}