{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-5ED16-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-5ED16-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-5ED16-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5ED16-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1180-5ED16-0AA0, molded case circuit breaker, 1-pole, 80 A, TM210 thermal-magnetic release, 121 kA at 240 V, 9 kA at 415 V, IP40 front.","salesMarkdown":"Its continuous current Iu is 80 A, and the TM210 thermal-magnetic release provides LI protection — meaning it handles overload (thermal) and short-circuit (magnetic) faults. The magnetic trip is fixed at 800 A (li), so it clears hard faults fast without adjustment. At 240 V the interrupting capacity is 121 kA; at 415 V it drops to 9 kA — the 415 V figure governs most European industrial panels, so verify your available fault current against that number. The breaker is 25.4 mm wide (1 inch) — a single-pole module that snaps onto a DIN rail, fitting standard 18 mm per-pole spacing. Depth is 70 mm, height 130 mm. Above that, derate linearly: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, 74 A at 70 °C. Maximum power loss is 6.4 W, which matters for thermal budgeting in a dense panel. Snap-on DIN rail mounting per EN 60715. The 25.4 mm width occupies one 18 mm pole pitch — standard for single-pole MCCBs. No auxiliary contacts are fitted (0 CO contacts), and no motor drive or communication module is included. The breaker is a standalone line-protection device; if you need remote tripping or status feedback, you'll add an external shunt trip or auxiliary switch separately.","metaTitle":"Siemens 3VA1180-5ED16-0AA0 SENTRON MCCB, 1-pole, 80 A, 121 k","metaDescription":"Siemens 3VA1180-5ED16-0AA0 SENTRON molded case circuit breaker, 1-pole, 80 A, TM210 release, 121 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"25.4 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"9 kA","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"1 in","Height [In]":"5.12 in","Number Of Poles":"1","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"6.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"80 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"125 V","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"800 A","Adjustable response value current / li min.":"800 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/693444f3f3c3849aa04ad9a33f7b0918.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=694657&mlfb=3VA1180-5ED16-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5ED16-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1180-5ED16-0AA0 at 240 V and 415 V?","answer":"At 240 V it is 121 kA; at 415 V it is 9 kA. The 415 V figure is the one to check for European industrial panel fault-current coordination."},{"question":"Where can I buy 3VA1180-5ED16-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-5ED16-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-5ED16-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}