{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-5ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-5ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-5ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1180-5ED22-0AA0, molded case circuit breaker (MCCB), 2-pole, 80 A rated current (TM210 release), 187 kA breaking capacity at 240 V AC, IP40 front protection, 70 mm depth × 50.8 mm width × 130 mm height.","salesMarkdown":"The 3VA1180-5ED22-0AA0: Breaking capacity is the headline here: 187 kA at 240 V AC and 121 kA at 415 V AC. The TM210 overcurrent release is a fixed thermal-magnetic type — no interchangeable trip units, no ground-fault module, no communication function. It is a straight line-protection device: thermal element handles overloads, magnetic element handles short-circuits. The 2-pole configuration and 500 V rated insulation voltage suit it for single-phase or two-leg three-phase branch circuits up to 415 V AC operating voltage. At 70 mm deep, 50.8 mm wide, and 130 mm tall, this MCCB fits a standard 2-pole DIN-rail footprint. The lifecycle stage is current. Siemens manufactures and supports this order code as an active catalog item.","metaTitle":"Siemens 3VA1180-5ED22-0AA0 SENTRON MCCB, 80A, 2-Pole, 187kA","metaDescription":"Siemens 3VA1180-5ED22-0AA0 SENTRON molded case circuit breaker, 80A rated current, 2-pole, 187kA breaking capacity at 240V AC. TM210 release, IP40 front. Active production, quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.8 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6d2e11e0a4936c7b4546118c49ed58ec.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=694658&mlfb=3VA1180-5ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What does the TM210 release designation mean?","answer":"TM210 is a fixed thermal-magnetic overcurrent release — the thermal element is sized for the 80 A frame, and the magnetic short-circuit pickup is factory-set. No interchangeable trip units or adjustment dials."},{"question":"Will 3VA1180-5ED22-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?","answer":"Both are 2-pole SENTRON MCCBs on the same 3VA platform, so the mounting footprint (70 mm × 50.8 mm × 130 mm) and DIN-rail clip are identical. The difference is the trip rating and breaking capacity — verify the downstream load and available fault current before swapping."},{"question":"Where can I buy 3VA1180-5ED22-0AA0 and how is it quoted?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — no stock count or lead-time number is published here, but the supply channel is active for this current-lifecycle item."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-5ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-5ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}